Project: a stepped retaining wall on a sloping residential block in Lowood, Somerset Region.
Our role: retaining wall design, Form 15 and pier inspection.
Wall type: galvanised steel posts and reinforced concrete sleepers on bored concrete piers.

Steel posts installed for a concrete sleeper retaining wall

The challenge

The block falls away steeply, so the wall height changes along its length, from about 1.0 m up to 2.6 m. Taller walls need deeper piers, heavier posts and closer post spacing, so one design would not suit the whole length.

What we did

  1. Used the site soil report to set the design soil values.
  2. Designed the wall to AS 4678 for a 60-year design life, with post size, post spacing and pier depth set for each range of wall height.
  3. Detailed the drainage behind the wall: free-draining gravel, geotextile, a slotted drain pipe and a spoon drain on top, so that water pressure cannot build up.
  4. Issued the drawings and Form 15, and inspected the pier holes before concrete was poured to confirm the ground matched the design.
Bored pier hole depth checked before concrete for a Form 12 inspection
Engineer measuring an installed steel post during an inspection

The result

An economical wall that steps with the slope of the block, built with standard galvanised steel sections and concrete sleepers.